Design Thickness |
N/A 0.0250 in |
Yield Strength |
N/A 57 ksi |
Area |
N/A 0.222 in² |
Weight |
N/A 0.76 lb/ft |
Gross Section Properties (lx) |
N/A 1.084 in4 |
Gross Section Properties (Sx) |
N/A 0.361 in³ |
Gross Section Properties (Rx)1 | N/A 2.208 in |
Gross Section Properties (ly) |
N/A 0.037 in4 |
Gross Section Properties (Ry) |
N/A 0.410 in |
Effective Section Properties at Tensile Strength (Fy) (Ae) |
N/A 0.068 in² |
Effective Section Properties at Tensile Strength (Fy) (lx) |
N/A 0.927 in4 |
Effective Section Properties at Tensile Strength (Fy) (Sx) |
N/A 0.208 in³ |
Effective Section Properties at Tensile Strength (Fy) (Mal)2 | N/A 7114 in·lb |
Effective Section Properties at Tensile Strength (Fy) (Mad)3 | N/A 6523 in·lb |
Effective Section Properties at Tensile Strength (Fy) (Vag) |
N/A 238 lb |
Effective Section Properties at Tensile Strength (Fy) (Vanet) |
N/A - lb |
Stud/Track End Reaction (Rx) |
N/A 116 lb |
Torsional Properties (Jx1000) |
N/A 0.0463 in4 |
Torsional Properties (Cw) |
N/A 0.272 in6 |
Torsional Properties (Xo) |
N/A -0.690 in |
Torsional Properties (m) |
N/A 0.448 in |
Torsional Properties (Ro) |
N/A 2.350 in |
Torsional Properties (ß) |
N/A 0.914 Beta |
Length (Lu) |
N/A 23.1 in |
Width |
N/A 6 in |
Spacing |
N/A 12 in16 in24 in |
Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 33 ft 5 in. |
Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 27 ft 4 in. |
Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 24 ft 2 in. |
Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 29 ft 2 in. |
Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 23 ft 11 in. |
Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 21 ft 1 in. |
Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 24 ft 2 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 21 ft 8 in. |
Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 2 in. |
Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 30 ft 4 in. |
Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 24 ft 10 in. |
Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 21 ft 11 in. |
Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 24 ft 2 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 21 ft 8 in. |
Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 19 ft 2 in. |
Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 18 ft 1 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 18 ft 1 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 17 ft 5 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 24 ft 2 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 21 ft 8 in. |
Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 19 ft 2 in. |
Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 16 ft 1 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 16 ft 1 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 16 ft 1 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 12 ft 1 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 12 ft 1 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 12 ft 1 in. (Adjacent to the height value indicates that shear/end reaction controls the allowable wall height.) |
Notes for Composite Limiting Height |
N/A
|
Fully Braced Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 27 ft 9 in. |
Fully Braced Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 23 ft 0 in. |
Fully Braced Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 20 ft 1 in. |
Fully Braced Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 22 ft 8 in. |
Fully Braced Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 22 ft 7 in. |
Fully Braced Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 9 in. |
Fully Braced Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 8 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 8 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 17 ft 11 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 24 ft 1 in. |
Fully Braced Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 20 ft 11 in. |
Fully Braced Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 18 ft 3 in. |
Fully Braced Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 19 ft 8 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 19 ft 8 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 17 ft 11 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 17 ft 0 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 17 ft 0 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 16 ft 4 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 19 ft 8 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 18 ft 3 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 15 ft 11 in. |
Fully Braced Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 16 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 16 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 15 ft 8 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 11 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 11 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 11 in. (Web stiffeners are required at the stud/track connection.) |
Notes for Fully Braced Non-Composite Limiting Height |
N/A
|
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 24 ft 2 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 23 ft 0 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 20 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 9 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 9 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 9 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 17 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 17 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 17 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 24 ft 2 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 23 ft 0 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 20 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 19 ft 9 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 19 ft 9 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 19 ft 9 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 17 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 17 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 17 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 17 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 17 ft 1 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 15 ft 11 in. |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 11 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 11 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 11 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 12 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 12 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 12 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
Notes for 48 Inch (in) O.C. Bracing Non-Composite Limiting Height |
N/A
|
Compliance |
N/A
TRAKLOC®’s ICC-ES Report # ESR-1464 is in compliance with:
|
United States (U.S.) and Foreign Patents |
N/A
The TRAKLOC® product line provided by ClarkDietrich® Building Systems is licensed under the following U.S. and Foreign Patents: U.S. Patent No. 7,223,043 U.S. Patent No. 7,594,311 U.S. Patent No. 8,061,099 U.S. Patent No. 8,074,416 Japan Patent No. 4934868 Japan Patent No. 5156889 Australia Patent No. 2006201344 Australia Patent No. 2005332657 |
TRAKLOC® Track |
N/A
TRAKLOC® track has two unique features. The most obvious feature of the TRAKLOC® track is the V-groove rolled into the flanges of the track to match the swaged ends of the TRAKLOC® stud. Next, are the dimples pressed into the center of the web. Together, the V-groove and the dimples provide a positive connection between stud and track without the need for mechanical fasteners. TRAKLOC® track standard length is 10'-0". Shorter lengths are available for non-standard conditions. |
Storage Requirements |
N/A TRAKLOC® is a dynamic system consisting of two moving parts. To maintain the telescoping feature of this system, it is important to store TRAKLOC® studs indoors, free of excessive dust and airborne particulates. |
Head-of-Wall Deflection Required ? |
N/A Elevator Studs are not for deflection by themselves. However, deflection can be achieved by using MaxTrak® slotted deflection track or deep leg track with lateral bracing at the head of the wall. |
Other Benefits Include |
N/A
|
Features and Benefits |
N/A
|
Addition Information |
N/A
The TRAKLOC® deflection stud is similar to our TRAKLOC® adjustable stud, except the 12" long extension insert has slots cut out of the flanges. This allows the drywall screw to pass through the drywall and the outer portion of the stud while passing through the slot. The slot allows the drywall to be attached while still allowing for seismic and/or live-load induced inter-floor deflection at the head-of-wall joint.
|
Note |
N/A
For SI Units: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 ksi = 6.89 N/mm².
|