Design Thickness |
N/A 0.0188 in |
Yield Strength |
N/A 33 ksi |
Area |
N/A 0.168 in² |
Weight |
N/A 0.57 lb/ft |
Gross Section Properties (lx) |
N/A 0.821 in4 |
Gross Section Properties (Sx) |
N/A 0.274 in³ |
Gross Section Properties (Rx)1 | N/A 2.212 in |
Gross Section Properties (ly) |
N/A 0.029 in4 |
Gross Section Properties (Ry) |
N/A 0.414 in |
Effective Section Properties at Tensile Strength (Fy) (Ae) |
N/A 0.057 in² |
Effective Section Properties at Tensile Strength (Fy) (lx) |
N/A 0.692 in4 |
Effective Section Properties at Tensile Strength (Fy) (Sx) |
N/A 0.156 in³ |
Effective Section Properties at Tensile Strength (Fy) (Mal)2 | N/A 2915 in·lb |
Effective Section Properties at Tensile Strength (Fy) (Mad)3 | N/A 2744 in·lb |
Effective Section Properties at Tensile Strength (Fy) (Vag) |
N/A 101 lb |
Effective Section Properties at Tensile Strength (Fy) (Vanet) |
N/A - lb |
Stud/Track End Reaction (Rx) |
N/A 75 lb |
Torsional Properties (Jx1000) |
N/A 0.0198 in4 |
Torsional Properties (Cw) |
N/A 0.208 in6 |
Torsional Properties (Xo) |
N/A -0.696 in |
Torsional Properties (m) |
N/A 0.452 in |
Torsional Properties (Ro) |
N/A 2.356 in |
Torsional Properties (ß) |
N/A 0.913 Beta |
Length (Lu) |
N/A 30.0 in |
Width |
N/A 6 in |
Spacing |
N/A 12 in16 in24 in |
Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 30 ft 5 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 25 ft 3 in. |
Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 22 ft 5 in. |
Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 24 ft 10 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 22 ft 0 in. |
Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 7 in. |
Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 21 ft 6 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 20 ft 0 in. |
Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 17 ft 9 in. |
Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 26 ft 4 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 23 ft 4 in. |
Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 20 ft 9 in. |
Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 21 ft 6 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 20 ft 5 in. |
Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 18 ft 2 in. |
Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 18 ft 7 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 18 ft 7 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 16 ft 6 in. |
Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 21 ft 6 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 20 ft 9 in. |
Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 18 ft 5 in. |
Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 17 ft 7 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 17 ft 7 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 16 ft 1 in. |
Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 15 ft 2 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 15 ft 2 in. (Adjacent to the height value indicates that flexural stress controls the allowable wall height.) |
Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 14 ft 5 in. |
Notes for Composite Limiting Height |
N/A
|
Fully Braced Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 2 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 2 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 18 ft 3 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 15 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 15 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 15 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 16 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 16 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 16 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 11 ft 9 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 11 ft 9 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 11 ft 9 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 11 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 11 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 11 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 9 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 9 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Fully Braced Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 9 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Notes for Fully Braced Non-Composite Limiting Height |
N/A
|
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 2 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 19 ft 2 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 18 ft 3 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 15 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 15 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 15 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 12 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 16 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 16 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 16 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 11 ft 9 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 11 ft 9 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 16 Inch (in) Spacing |
N/A 11 ft 9 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 13 ft 6 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 11 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 11 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 7.5 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 11 ft 1 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/120) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 9 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/240) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 9 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
48 Inch (in) O.C. Bracing Non-Composite Limiting Height (L/360) at 10 Pounds Per Square Foot (PSF) Pressure and 24 Inch (in) Spacing |
N/A 9 ft 7 in. (Web stiffeners are required at the stud/track connection.) |
Notes for 48 Inch (in) O.C. Bracing Non-Composite Limiting Height |
N/A
|
Compliance |
N/A
TRAKLOC®’s ICC-ES Report # ESR-1464 is in compliance with:
|
United States (U.S.) and Foreign Patents |
N/A
The TRAKLOC® product line provided by ClarkDietrich® Building Systems is licensed under the following U.S. and Foreign Patents: U.S. Patent No. 7,223,043 U.S. Patent No. 7,594,311 U.S. Patent No. 8,061,099 U.S. Patent No. 8,074,416 Japan Patent No. 4934868 Japan Patent No. 5156889 Australia Patent No. 2006201344 Australia Patent No. 2005332657 |
TRAKLOC® Track |
N/A
TRAKLOC® track has two unique features. The most obvious feature of the TRAKLOC® track is the V-groove rolled into the flanges of the track to match the swaged ends of the TRAKLOC® stud. Next, are the dimples pressed into the center of the web. Together, the V-groove and the dimples provide a positive connection between stud and track without the need for mechanical fasteners. TRAKLOC® track standard length is 10'-0". Shorter lengths are available for non-standard conditions. |
Storage Requirements |
N/A TRAKLOC® is a dynamic system consisting of two moving parts. To maintain the telescoping feature of this system, it is important to store TRAKLOC® studs indoors, free of excessive dust and airborne particulates. |
Head-of-Wall Deflection Required ? |
N/A Elevator Studs are not for deflection by themselves. However, deflection can be achieved by using MaxTrak® slotted deflection track or deep leg track with lateral bracing at the head of the wall. |
Other Benefits Include |
N/A
|
Features and Benefits |
N/A
|
Addition Information |
N/A
TRAKLOC® stud without telescopic extension. Studs are fixed length and not adjustable and have a TRAKLOC® swaged end on both ends of the stud allowing the stud to be connected to the top and bottom track without fasteners.
|
Note |
N/A
For SI Units: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 ksi = 6.89 N/mm².
|